Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Remove standing water from pit. Provide means to allow water to flow into sump hole
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test and log firefighter operation monthly
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 1001.2(c)(15) Identify inside of hoistway doors with a numeral
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits REMOVE STANDING OIL FROM PIT FLOOR
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate. 1/19/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 1/28/2021
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Remove cylinder drain line from tank. Cylinder line needs to drain into pit container of no more than 5 gallon capacity. 3/23/2021
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 100.7 Identify inside of hoistway doors with corresponding landing level. 3/23/2021