Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Water standing in pit, remove. Sump pump most likely not working. 4/3/2026
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) No No Prove safe access to machine room. Relamp landing lights as needed 4/3/2026
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code No No Provide code compliant machine room lighting 4/3/2026
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) No No Provide safe access to machine room, replace burnt out bulbs 4/3/2026
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code No No Provide code compliant machine room lighting 4/3/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No There is standing water in pit, sump pump isn't working 4/3/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. Re-inspection required 4/3/2026
A17.1-1996 : Elevators 1.7 - Car door or gate 1001.2(a)(7) No No The gap between the door and the cop exceeds 10 mm. Re-inspection required 4/3/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit light does not work 4/3/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work.
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 107.1b Yes No Counterweight runby shall not be less than 6". Currently 4".
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No There is standing water in pit, sump pump isn't working. Pit shall be kept dry. Repair Sump, Clean pit, remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No Machine room lighting needs to be repaired, 1 or more bulbs not working.
A17.1-1996 : Elevators 1.7 - Car door or gate 1001.2(a)(7) No No The gap between the door and the cop exceeds 10 mm.
A17.1-1996 : Elevators 3.23 - Suspension rope 212 Yes No Hoist Rope Tail retaining clips shall be properly spaced (car side)
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit light shall work
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No Fire Service testing must be properly documented monthly on Log Sheet located in the MCP. No Log present.
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 No No Cab Lighting cartop wiring box is missing cover, wires hanging out.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Items to be completed: 100% Safety Set, Slide, 125% items.