A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
No
|
No
|
Water standing in pit, remove. Sump pump most likely not working.
|
4/3/2026
|
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
No
|
No
|
Prove safe access to machine room. Relamp landing lights as needed
|
4/3/2026
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
No
|
No
|
Provide code compliant machine room lighting
|
4/3/2026
|
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
No
|
No
|
Provide safe access to machine room, replace burnt out bulbs
|
4/3/2026
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
No
|
No
|
Provide code compliant machine room lighting
|
4/3/2026
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
No
|
No
|
There is standing water in pit, sump pump isn't working
|
4/3/2026
|
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
1001.2(a)(7)
|
No
|
No
|
The gap between the door and the cop exceeds 10 mm. Re-inspection required
|
4/3/2026
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
No
|
No
|
Pit light does not work
|
4/3/2026
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
No
|
No
|
There is standing water in pit, sump pump isn't working. Pit shall be kept dry. Repair Sump, Clean pit, remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak.
|
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
No
|
No
|
Machine room lighting needs to be repaired, 1 or more bulbs not working.
|
|
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
1001.2(a)(7)
|
No
|
No
|
The gap between the door and the cop exceeds 10 mm.
|
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
No
|
No
|
Pit light shall work
|
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
No
|
No
|
Fire Service testing must be properly documented monthly on Log Sheet located in the MCP. No Log present.
|
|
|
A17.1-1996 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
102
|
No
|
No
|
Cab Lighting cartop wiring box is missing cover, wires hanging out.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Items to be completed: 100% Safety Set, Slide, 125% items.
|
|
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
212
|
Yes
|
No
|
Hoist Rope Tail retaining clips shall be properly spaced (car side)
|
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone does not work.
|
|
|
A17.1-1996 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
107.1b
|
Yes
|
No
|
Counterweight runby shall not be less than 6". Currently 4".
|
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone does not work. Re-inspection required
|
4/3/2026
|