A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4
|
Yes
|
No
|
2.2.4.5 - Walk in pit door shall be self-closing and self-locking with means to disable service car operation before entering pit.
|
10/19/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/19/2023
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
9/19/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/19/2023
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)1
|
No
|
No
|
Cab ventilation fan is not operational and shall be repaired.
|
1/12/2021
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.3
|
Yes
|
No
|
Install proper steps from controller level to machine level.
|
10/19/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
Yes
|
Yes
|
Smokes were tested with magnet but must be tested by fire device company with smoke when all units are ready for acceptance test.
|
10/19/2023
|
|
A17.1-2016 : Elevators
|
2.29 - Car and counterweight safeties
|
8.6.4.20.1
|
Yes
|
No
|
Test car safeties by tripping car overspeed governor and turning car down on inspection speed with no load in the car. Re-inspection required
|
|
|
A17.1-2016 : Elevators
|
3.20 - Governor rope
|
8.6.3.4
|
Yes
|
No
|
The elevator safety pull out connection to the governor rope has been replaced with fist grip type connections that are now impeding the pulling out of the governor rope to set the wind up safeties. The governor rope attachments shall be replaced with a code compliant system that allows the governor rope to be pulled out without interference. Re-inspection required
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The inspection was not completed due to problems at the time. The following tests still need to be completed: Fire service, unintended movement, door pressure, lighting & phone. Re-inspection required
|
11/18/2024
|