MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A17.1 - 2004 8.6.1.2 GENERAL MAINTENANCE REQUIREMENTS 8.6.1.2.1(1)(b) INSTRUCTIONS FOR LOCATING REMOTELY KEPT MCP RECORDS SHALL BE PROVIDED IN OR ON THE CONTROLLER. 3/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods A17.1 - 2004 8.6.1.6 GENERAL MAINTENANCE METHODS & PROCEDURES CAT 1 NO LOAD & CAT 5 FULL LOAD TESTING PROCEDURES ARE REQUIRED AS ON SITE DOCUMENTATION 3/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby INSUFFICENT, LESS THAN 6 IN. OBSERVED 2" RUNBY, HOIST ROPES SHALL BE SHORTENED. 6/20/2022