Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency communications/phone in car not working. 5/5/2026
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 No No Observed several bottom door guides (on different floors) don’t have fire tabs bent down, make so. 4/7/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean car top. 4/7/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Clean upper and lower pits. 4/7/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide testing of the elevator on emergency power. 4/7/2026
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.6.4.20.1 Yes No Provide Cat 5 safety test, record slide. 4/7/2026
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.6.4.13 No No Observed bottom door guides ( on several floors) don’t have fire tabs bent down, make so. 4/7/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean the car top. 4/7/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Clean upper and lower pits. 4/7/2026
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2 through 2.27.8 Firefighter Service Yes Yes On Phase II operations, door close function not working. Car removed from service. 9/10/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide testing of the elevator on emergency power. 9/10/2024
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.6.4.20.1 Yes No Provide Cat 5 testing of the car safeties. Record slide. Check rails for dressing. 9/10/2024
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.12 Yes No Remote governor trip not functioning. 11/30/2021