Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work and give proper location 8/12/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work and give proper location 8/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car Door restrictor shall work. Bracket missing 8/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Pit scavenger pump will be removed 8/9/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car Door restrictor shall work. Bracket missing 8/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No maintenance records 2/23/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x B(11): 2-way communication device shall work and give proper location, 1st and 2nd numbers: No Answer. must be answered 24/7. (Reported as repaired previously , but not) REINSPECTION REQUIRED, 30days 12/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x G(1) Car Door restrictor shall work. Wrong bracket installed. (Reported as repaired previously , but not) REINSPECTION REQUIRED, 30days 12/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records G(1)/A17.1-2016:8.6.1.4 :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) . 2/23/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 H4. Machine room shall not be used to store non-elevator related items. ( fluorescent lamps, ceiling tiles, AC parts, ) 2/23/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log To be tested monthly 2/23/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post updated certificate 2/23/2023