Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) x Emergency standby power needs to be tested. Re-inspection required
A17.1-2016 : Elevators 3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.11.2.1.3(t) Seismic test failed. Did not hold car at floor, went into normal operation, needs repaired. Re-inspection required
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in the elevator cab does not work. Re-inspection required 4/4/2025
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes are rouged and undersized, need to replace suspension ropes. Re-inspection required 4/4/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following tests need to be performed to complete the 5 year inspection: 125% brake / lower and hold, car safeties, counterweight buffer & car buffer. Re-inspection required 6/26/2023