Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space the machinery space is not separated from the rest of the room, item were piled on and around the elevator equipment with no clear work space 4/12/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) the pit light was not working, the light bulb was burnt out 4/12/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records need to start maintenance control program, there was no records on site 4/12/2021
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.11.3.1.1(e) replace burnt out cab ceiling light blub 4/12/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.3.1.5(a) pit light bulb is burnt out and needs to be replaced 6/3/2021
A17.1-1996 : Elevators 3.3 - Top-of-car operating device 204.1g Top of car inspections not working. Did test safeties. 8/31/2020
A17.1-1996 : Elevators 3.3 - Top-of-car operating device 210.1d Top of Car Inspection Operation not working properly. Will not move past the next floor's door zone switch in either direction. 8/31/2020
A17.1-2016 : Elevators 3.17 - Door and gate equipment 8.11.3.1.3(r) could not get the door on the 2nd landing to open automatically, had to push them open. door operator worked fine on the other landing on that side. could not find any obstructions preventing that door from opening. 6/3/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 x Pit Light not working. 11/24/2020
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.11.2.1.2(gg) x x the 5 year test was due in 2021, don't have record of it being done. slack rope type safeties.