MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Inspection is incomplete. Elevator #1 is in the middle of a drive sheave repair. Re-inspection required
|
2/6/2026
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
Yes
|
No
|
Suspension ropes are rouged and undersized, need to replace suspension ropes. Re-inspection required
|
2/6/2026
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
Yes
|
No
|
Suspension ropes are rouged and undersized, need to replace suspension ropes. Re-inspection required
|
1/22/2026
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
No
|
No
|
Repair machine room lighting above machine and in front of controller
|
1/8/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A copy of the current state operating certificate shall be displayed in the machine room
|
1/8/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A copy of the current state operating certificate shall be displayed in the machine room
|
1/8/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The following tests need to be performed to complete the 5 year inspection: 125% brake / lower & hold, car safeties, car buffer and counterweight buffer. Re-inspection required
|
6/26/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone is inoperable. Re-inspection required
|
|