MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Test the car safeties and provide means (tool) to wind up safeties for testing.
|
5/5/2022
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Steps leading up to machine room need to be permanently installed with a handrail to prevent safety hazards
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Several floors have the wired class panels, need to replace with solid glass, that is not etched or labeled. Provide proper labeling or replace if glass does not meet the ANSI requirements.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Replace or repair all hoistway door glass vision panels as needed.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Repair or replace slide guide on left side of car. Guide is worn out and barely touches rail
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove non elevator items from machine room.
|
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove fluids from the pit. Provide means of waterproofing to prevent further entry of fluids.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Remove broken traveling cable in hoistway that's still attached to the bottom side of cab
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove broken light fixture from ceiling .
|
|
|
MO Minimum : Elevators
|
(J) - Counterweights
|
(J)2
|
|
|
Provide spin out cable through the rope shackles on the counterweights
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
x
|
|
Provide safe and convenient access to secondary level, proper steps w/handrail. SECOND NOTICE.
|
9/5/2023
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)10 Car Floors
|
|
|
Provide means to substantially level floor. Pull out hole creates a tripping hazard.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
Provide means to secure the emergency exit.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
x
|
|
Provide current year MCP.
|
9/5/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
x
|
|
Provide current tested (not new out of the box) fire extinguisher in the elevator machine room.
|
9/5/2023
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Provide code compliant ladder or steps to access elevated machine platform in machine room.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)10
|
|
|
Provide code compliant hoistway access.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)4
|
|
x
|
Provide bottom door guides on "B" floor hoistway door.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Provide a current tested fire extinguisher in the machine room.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit has at least 6" of water in it, needs to be kept clean & dry
|
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Operating certificate shall be posted in machine room
|
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.12
|
x
|
|
Need to replace defective governor, not operating properly
|
3/19/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
|
|
Machine room shall be kept clean & free of debris and trash
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room shall be cleaned of trash and old broken elevator controller.
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)3
|
|
|
Machine room floor shall have open hole properly covered.
|
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self-closing and self-locking.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self closing and self locking.
|
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
x
|
|
Hoistway door sill catch on bottom floor needs to be secured to sill.
|
9/5/2023
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Hoistway door glass shall be replaced with tempered glass.
|
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Governor rope is undersized, needs to be replaced. Re-inspection required
|
1/16/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher is expired.
|
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
x
|
|
Existing hoist way doors require safety glass installed, provide proof that existing pane glass in hoist way door is CODE compliant. Numerous floors.
|
9/5/2023
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
9/15/2021
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)4
|
|
x
|
Counterweight buffers are rusted through and broken, will not support elevator. Red tagged, Re-inspection required
|
1/16/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
110.11a Need to secure 1st floor sill to floor
|
|