MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
The exposed wiring on the car top and in the hoistway at the 2nd landing shall be enclosed.
|
9/15/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
All wireway and electrical device covers must be installed.
|
9/15/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Remove exposed wiring and splices from car top and replace with proper NEC wiring
|
9/27/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Electrical wiring provided for new cab lighting shall be protected & open splices enclosed in junction boxes per NFPA 70
|
7/1/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
The emergency exit shall be capable of sustaining a load of 300 lbs.
|
9/15/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)9 Capacity Plate
|
|
|
Provide means for substantially level floor. Pull out hole creates a tripping hazard.
|
9/15/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
Emergency exit is not code compliant.
|
9/15/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Provide a current tested fire extinguisher in the machine room.
|
9/15/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide MCP.
|
6/1/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Provide a current tested ABC fire extinguisher in the machine room.
|
9/15/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
|
|
The car safety key shall be kept on-site.
|
9/15/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Provide safe and convenient access to the elevator machine room, wooden steps leading in are damaged.
|
6/1/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
First plank into the machine room needs to be secured down. Trip hazard.
|
6/1/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self locking / self closing
|
7/1/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Provide a minimum of 10 ft candles of illumination measured at the floor through out the machine room
|
9/27/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Wooden stairway treads to access machine and controller are worn and damaged and shall be replaced or repaired as needed.
|
9/15/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self-locking and self-closing.
|
9/15/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove all material from the machine room which is not required for the operation of maintenance of the elevator.
|
9/15/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
The wooden steps going up to the machine room deck are damaged and shall be replaced.
|
9/15/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Provide code compliant lighting in the machine room (10 FTC minimum).
|
9/15/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The debris in the pit shall be removed. The pit shall be kept clean.
|
9/15/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit lighting shall be operational.
|
9/15/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit light shall work.
|
9/15/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Provide existing pit light to work.
|
6/1/2024
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Test the car safeties and provides means (tool) to wind up safeties for testing.
|
2/19/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The governor rope pullout shall be 42" or less.
|
9/7/2021
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Install proper emergency exit cover. Must be designed to support weight and secured so that it can only be opened from the car top without the use of tools.
|
12/12/2018
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
9/15/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
9/15/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
6/1/2024
|