A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Battery lowering does not work, repair & re-inspect
|
1/9/2024
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Battery lowering shall work. Take corrective action as needed.
|
2/19/2025
|
A17.1-1996 : Elevators
|
3.2 - Car top light and outlet
|
204.7
|
|
|
Car top light does not work.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work. Re-inspection required
|
1/9/2024
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
Fire service testing must be documented monthly.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Machine room shall not be used for storage. Have been written up multiple times
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Non-elevator related items shall not be stored in machine room.
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2b (Clean Machine Room)
|
|
|
Non-elevator related items shall not be stored in the machine room.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be clean and free from oil, there is about 2" of oil covering pit floor. Re-inspection required
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Pit sump cover shall be repaired to be flush with pit floor.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Pit sump cover shall be repaired to be flush with pit floor.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
The pit shall be kept clean. Remove excess debris.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
The pit shall be kept clean. Remove excess debris.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work. Multi-year violation.
|
2/19/2025
|