Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) lighting in the machine room does not meet the 10 foot candle minimum, measured 6 foot candles at the controller 11/11/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x only one emergency light bulb came on, replace burnt out emergency light bulb 12/4/2023