MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
: 2-way communication device shall work and give proper location (REINSPECTION REQUIRED)
|
4/30/2021
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2(B)
|
|
|
Relief/bypass pressure shall be adjusted to no more than 125% of working pressure
|
4/30/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
: 2-way communication device shall work and give proper location (REINSPECTION REQUIRED)
|
4/30/2021
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2(B)
|
|
|
Relief/bypass pressure shall be adjusted to no more than 125% of working pressure
|
4/30/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
G/2.7.1/8.6.1.6.5: Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired)
|
8/4/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
A(16)/NFPA70 : Black wiring in hoistway (camera coax? ) shall be inside metal conduit/flex
|
8/4/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone failed
|
9/3/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
provide current operating certificate
|
10/11/2024
|