MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
The car door reopening device (light ray) is not operational allowing the car door to continue to close when an object is blocking the entrance. Repair the reopening device to operate for passenger safety
|
3/2/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
The car door reopening device (light ray) is not operational allowing the car door to continue to close when an object is blocking the entrance. Repair device
|
3/2/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals.
|
3/2/2022
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site maintenance control program.
|
5/20/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A written MCP shall be kept onsite
|
3/2/2022
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed. Perform test on or before next annual inspection date.
|
5/20/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
This elevator has an overspeed valve device installed that is not sealed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested.
|
12/13/2021
|