Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) Access door for dumbwaiter machine space located at the bottom of the hoistway needs to be kept closed and locked, and electrical contact on access door is required and shall interrupt power to motor and brake. Key to unlock the access door shall be a Group 1 security key. 9/30/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Provide code data plate on controller or disconnect. "A17.1 1996" 10/31/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(1) Provide on site documentation of maintence records that correspond to the maintenance control plan. 10/31/2020
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 Machine motor leads need to be in metal conduit 11/10/2022