MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6.
|
4/28/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine Room shall be kept clean of any accumulation of oil, grease, or dust. Excessive amount of rope dust on equipment and floor
|
4/28/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Cover or replace in car lantern arrow holes
|
4/28/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace hoist rope shackle isolation pads that have deteriorated
|
4/28/2023
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
Hoist Ropes have excessive rouge and have stretched reducing diameter beyond maximum allowable amount. Replace Hoist ropes.
|
9/25/2023
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.2-211.8
|
x
|
|
PHASE I FIRE SERVICE KEY SWITCH DOESN'T WORK
|
12/11/2018
|