Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. 4/28/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Cover or replace in car lantern arrow holes 4/28/2023
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x Hoist Ropes have excessive rouge and have stretched reducing diameter beyond maximum allowable amount. Replace Hoist ropes. 9/25/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine Room shall be kept clean of any accumulation of oil, grease, or dust. Excessive amount of rope dust on equipment and floor 4/28/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 x PHASE I FIRE SERVICE KEY SWITCH DOESN'T WORK 12/11/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace hoist rope shackle isolation pads that have deteriorated 4/28/2023