MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. 10/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency communication device not functioning. Phone rings but no one answers. Repair or replace. Reinspection required. 10/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. 10/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency communication device not functioning. Phone rings but no one answers. Repair or replace. 14 days have been given with no repair. 10/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. 11/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x x Emergency communication device not functioning. Phone rings but no one answers. Repair or replace. 14 days have been given with no repair. The elevator shall remain out of service until the phone has been repaired. 11/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.4.19.6 Fire service bezel unreadable and shall be replaced.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. 10/16/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. 10/18/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. 11/5/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 10/16/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Note: This is part of a Category 5 and Category 1 test. 11/5/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Note: This is part of a Category 5 and Category 1 test. 10/18/2025
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light shall be made operable. Re-inspection required 12/9/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Upon performing the annual inspection, it was noted that no documentation exists even though the inspection tags on the equipment indicate the Category 5 test was completed. Therefore, without any other documentation, it shall be determined that the Category 5 test has not been completed. Either provide documentation from a QEI licensed inspector that the test has been completed or a reinspection shall be required within 15 days to complete the Category 5 test. Failure to comply in this time frame will result in the elevator placed out of service with a red tag issued. 10/16/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x x This unit has not had a documented Category 5 test since 2/11/2013. The Category 5 test shall be completed before the elevator can be returned to service. 10/18/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x x This unit has not had a completed Category 5 test since 2/11/2013. The Category 5 test shall be completed before the elevator can be returned to service. To complete this Category 5 requires the emergency power operation test to be completed. 11/5/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Repair pit light. 8/21/2025