Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Repair pit light. 8/21/2025
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light shall be made operable. Re-inspection required 12/9/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 10/16/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Note: This is part of a Category 5 and Category 1 test. 10/18/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x x This unit has not had a documented Category 5 test since 2/11/2013. The Category 5 test shall be completed before the elevator can be returned to service. 10/18/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. 10/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. 10/18/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency communication device not functioning. Phone rings but no one answers. Repair or replace. 14 days have been given with no repair. 10/18/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator machine room shall be self closing and self locking. Door self closing device on floor in machine room. Repair or replace. 10/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.4.19.6 Fire service bezel unreadable and shall be replaced. 10/16/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency communication device not functioning. Phone rings but no one answers. Repair or replace. Reinspection required. 10/16/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Upon performing the annual inspection, it was noted that no documentation exists even though the inspection tags on the equipment indicate the Category 5 test was completed. Therefore, without any other documentation, it shall be determined that the Category 5 test has not been completed. Either provide documentation from a QEI licensed inspector that the test has been completed or a reinspection shall be required within 15 days to complete the Category 5 test. Failure to comply in this time frame will result in the elevator placed out of service with a red tag issued. 10/16/2025