A17.1-1996 : Elevators
|
3.1 - Top-of-car stop switch
|
1001.2(c)(1)
|
|
|
Repair car stop switch on door operator box.
|
|
A17.1-1996 : Elevators
|
3.1 - Top-of-car stop switch
|
210.2(h)
|
|
|
Cartop stop switch on door operator is still broken. Repair/replace same. Second notice.
|
|
A17.1-1996 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
107.1b
|
x
|
|
Counterweight runby is 2", hoist ropes need to be shortened to have between 6" & 11" runby. Re-inspection required
|
12/9/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light shall be made operable. Re-inspection required
|
7/31/2023
|