Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light shall be made operable. Re-inspection required 7/31/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone does not work, needs repaired. Re-inspection required
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No On phase II fire service, one of the two door close buttons did not work, needs repaired. Re-inspection required
A17.1-1996 : Elevators 3.1 - Top-of-car stop switch 210.2(h) No No Cartop stop switch on door operator is still broken. Repair/replace same. Second notice. 8/21/2025
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 107.1b Yes No Counterweight runby is 2", hoist ropes need to be shortened to have between 6" & 11" runby. Re-inspection required 12/9/2024
A17.1-1996 : Elevators 3.1 - Top-of-car stop switch 1001.2(c)(1) No No Repair car stop switch on door operator box. 8/21/2025