MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Incomplete 5 year inspection. Still needs buffers smashed, 125% hold , setting safeties, slide recorded, and unintended motion tested.
|
|
A17.1-1996 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.4.10.1.2 - Protection not functioning
|
x
|
|
Earthquake protection is not working. Re-inspection required
|
12/17/2024
|
A17.1-1996 : Elevators
|
3.8 - Top emergency exit
|
204.1e
|
|
|
Emergency exit hatch switch does not disconnect driving machine power. Repair
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the elevator machine room
|
|