Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop needs to be cleaned 6/23/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not call the correct elevator maintenance company. 4/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone in car does not work, appears to not have live phone line. Re-inspection required 6/28/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 9/13/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Label the main electrical disconnect with the source panel and breaker. 1/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform OSV test on or before next annual inspection. 9/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Pit light shall work. 9/16/2021
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned 6/23/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.16 - Rated load, platform area, and data plate 8.11.2.1.1(p) The capacity sign in the cab is illegible. 1/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops The car top shall be cleaned. 1/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) The heat detector in the machine room shall not affect the operation of the elevator or the shunt trip since there is not a sprinkler head present. 1/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 The heat detector in the machine room shall not affect the operation of the elevator or the shunt trip since there is not a sprinkler head present. - Re-Inspection Required 1/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits The pit shall be kept clean. 1/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) Upper and lower hoistway access does not stop. Adjust for code compliant stop. 1/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) Upper and lower hoistway access switches shall be momentary/spring return. 1/19/2021