A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Post emergency evacuation of passengers procedure inside machine room.
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Test and log firefighter operation monthly.
|
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
Cylinder drain line needs to drain into pit container of no more than 5 gallon capacity.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Post firefighter operating instructions on car operating panel.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Post firefighter operating instructions next to hall fire keyswitch.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate inside machine room.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Test and log firefighter operation monthly
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Post emergency evacuation of passengers procedure in machine room
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the machine room
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
1000.1b(3)(b) Metal Test Tag
|
|
|
Install metal test tag for periodic pressure relief test
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No MCP
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No maintenance records on site
|
|
A17.1-1996 : Elevators
|
3.9 - Floor and emergency identification numbering
|
100.7
|
|
|
Identify inside of hoistway doors with a numeral
|
|
conversion
|
conversion
|
n/a
|
|
|
phone does not operate
|
1/15/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Post firefighter instructions on car operating panel
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Post firefighter instructions next to hall firefighter keyswitch
|
|
A17.1-1996 : Elevators
|
3.9 - Floor and emergency identification numbering
|
100.7
|
|
|
Identify inside of hoistway door with a numeral
|
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Machine room door needs to be self-locking
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed in machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Post In Case of Fire signage next to hall button fixture at each landing
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
"B" jamb tags missing due to vandalism.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.5.14.3(f)
|
x
|
|
Auxiliary lowering unit does not operate
|
10/23/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.5.14.3(f)
|
x
|
|
Battery lowering not working.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
10/23/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not function
|
1/21/2019
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Emergency auxillary power does not operate
|
1/21/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
8/11/2023
|