Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 100.7 Identify inside of hoistway doors with a numeral
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 100.7 Identify inside of hoistway door with a numeral
A17.1-1996 : Elevators 2.41 - Maintenance Records 1000.1b(3)(b) Metal Test Tag Install metal test tag for periodic pressure relief test
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Emergency auxillary power does not operate 1/21/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not function 1/21/2019
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room door needs to be self-locking
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 10/23/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 8/11/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Post firefighter instructions on car operating panel
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Post firefighter instructions next to hall firefighter keyswitch
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Post firefighter operating instructions on car operating panel.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Post firefighter operating instructions next to hall fire keyswitch.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate inside machine room.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed in machine room
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No MCP
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Test and log firefighter operation monthly
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post emergency evacuation of passengers procedure in machine room
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post emergency evacuation of passengers procedure inside machine room.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No maintenance records on site
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to hall button fixture at each landing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates "B" jamb tags missing due to vandalism.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test and log firefighter operation monthly.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x Auxiliary lowering unit does not operate 10/23/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x Battery lowering not working.
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Cylinder drain line needs to drain into pit container of no more than 5 gallon capacity.
conversion conversion n/a phone does not operate 1/15/2020