Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x emergency phone did not work, phone line is dead, provice working phone line to the elevator controller 9/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements car top work light is burnt out and needs to be replaced 11/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements the emergency light battery is dead and needs to be replaced 11/7/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the state operating certificate on display in the machine room expired in 2019, update with new copy when received from the state annually 11/7/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 the self closer on the machine room door has pulled the mounting screws out of the door, reattach closer to the door, may have to through bolt the mount to the door, it has been drilled several times 11/7/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x emergency phone hangs up immediately, has dial tone and voltage on the phone line, repair or replace phone in the elevator 11/11/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 do not store non elevator related material in the machine room, (empty cardboard boxes) 7/15/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a copy of the state operating certificate is to be posted in the machine room 7/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers service the fire extinguisher in the machine room, the indicator gauge is in the red, says it has been discharged 7/15/2023