Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x car door locking device not working 3/15/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 machroom door lock is defeatable
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 need to replace in case of fire use stairs signage
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate no current cirt displayed 3/28/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records no current mcp on site 5/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection oil pumpback sys needs to be removed from pit 5/12/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x phone not working 3/28/2022