Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a 1) Maintenance records shall document compliance with 8.6 of the Code shall be available to the inspector at time of inspection. 7/10/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x Phase II call cancel not working 4/25/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Sump pump not working. Remove standing water from pit