Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Main hoisting ropes undersized. .594 5/20/2019
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Phase II fire service not working. 5/20/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Repair the emergency lights and bell.
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)7 Yes Yes Seal missing on governor adjustment means. 5/13/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)4 No No Car door gibs badly worn. 10/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Cartop light not working. 10/29/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)11 No No Cartop wedge shackles missing cotter pins on jam nuts. 10/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean car top, debris present. 10/21/2021
MO Minimum : Elevators (I) - Pits (I)1 No No Debris in pit. 10/21/2021
MO Minimum : Elevators (A) - Hoistways (A)3 No No Hoistway door gibs worn. 10/29/2020
MO Minimum : Elevators (A) - Hoistways (A)1 No No Landing door gibs badly worn, all floors. 10/29/2020
MO Minimum : Elevators (A) - Hoistways (A)1 No No Landing door missing pick up roller. FL 4 10/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Machine room controller inspection switch not working. Repair. 10/29/2020
MO Minimum : Elevators (A) - Hoistways (A)3 No No Pick up roller missing on 4th floor landing door. 10/29/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light not working. 10/21/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate in machine room. 8/30/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Provide fire service testing log in machine room, and document monthly testing. 10/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide MCP, or location of MCP in machine room. 10/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Reinstall existing rope guards on machine. (leaning against wall) 10/29/2020