MO Minimum : Elevators
|
(A) - Hoistways
|
(A)1
|
|
|
Landing door gibs badly worn, all floors.
|
10/29/2020
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Hoistway upthrust devices worn, allowing center opening doors to open more than 2" without interrupting operation of elevator.
|
10/29/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm not working.
|
5/20/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
Car door reopening device damaged, but functional. Repair.
|
10/29/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)6
|
|
|
Door re-opening device broken, exposing sharp edges.
|
10/29/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
Upthrust devices on landing doors out of adjustment, and allowing doors to open 2" at sill level without stopping operation of the elevator.
|
8/6/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Door reopening device on car door broken, sharp edges exist.
|
8/6/2021
|
MO Minimum : Elevators
|
(J) - Counterweights
|
(J)3
|
|
|
CW runby below minimum.
|
10/29/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
No CW runby in pit.
|
5/20/2020
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)5
|
x
|
x
|
SOS switch not opening safety circuit upon activation of the car safeties.
|
2/26/2021
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)5
|
x
|
x
|
SOS switch not opening upon activation of the car safeties.
|
8/6/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide MCP, or location of MCP in machine room.
|
10/29/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Provide fire service testing log in machine room, and document monthly testing.
|
10/29/2020
|