Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 Car door reopening device damaged, but functional. Repair. 10/29/2020
MO Minimum : Elevators (J) - Counterweights (J)3 CW runby below minimum. 10/29/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 Door re-opening device broken, exposing sharp edges. 10/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door reopening device on car door broken, sharp edges exist. 8/6/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency alarm not working. 5/20/2020
MO Minimum : Elevators (A) - Hoistways (A)3 Hoistway upthrust devices worn, allowing center opening doors to open more than 2" without interrupting operation of elevator. 10/29/2020
MO Minimum : Elevators (A) - Hoistways (A)1 Landing door gibs badly worn, all floors. 10/29/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x No CW runby in pit. 5/20/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Provide fire service testing log in machine room, and document monthly testing. 10/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide MCP, or location of MCP in machine room. 10/29/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)5 x x SOS switch not opening safety circuit upon activation of the car safeties. 2/26/2021
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)5 x x SOS switch not opening upon activation of the car safeties. 8/6/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Upthrust devices on landing doors out of adjustment, and allowing doors to open 2" at sill level without stopping operation of the elevator. 8/6/2021