Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve. Based on the installation date of 2008, the overspeed valve is due for a category 5 test on or before the next annual inspection.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed and witnessed within 90 days. 9/11/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) x x Firemans Phase 1 bezel is missing and shall be replaced. 11/17/2020
conversion conversion conversion - reinspect x Existing cab emergency telephone doe not work and shall be repaired and tested. 7/20/2018
conversion conversion n/a Phase 1 key station has a broken jewel bezel on the fireman's hat indicator, said jewel shall be replaced. 11/17/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.