conversion
|
conversion
|
n/a
|
|
|
Phase 1 key station has a broken jewel bezel on the fireman's hat indicator, said jewel shall be replaced.
|
11/17/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an overspeed valve. Based on the installation date of 2008, the overspeed valve is due for a category 5 test on or before the next annual inspection.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Existing cab emergency telephone doe not work and shall be repaired and tested.
|
7/20/2018
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed and witnessed within 90 days.
|
9/11/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.1.4(l)
|
x
|
x
|
Firemans Phase 1 bezel is missing and shall be replaced.
|
11/17/2020
|