conversion
|
conversion
|
n/a
|
|
|
Need "Low Overhead" clearly posted in hoistway
|
12/14/2018
|
conversion
|
conversion
|
n/a
|
|
|
Post MO State operating permit in machine room
|
12/14/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light not working.
|
6/15/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room shall not be used for storage of non-elevator equipment.
|
9/30/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)1
|
|
|
Cab ventilation not working.
|
9/30/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
|
|
AC unit cannot be located directly over the pump unit in the elevator machine room. Move AC unit
|
9/8/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
Air conditioning systems shall not be located directly over elevator equipment.
|
9/8/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.5 - Traveling cables
|
2.8.1
|
|
|
Both traveling cables are rubbing conduit in elevator hoistway. Move cables to prevent further damage
|
10/29/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.5 - Traveling cables
|
8.11.2.1.5(f)
|
|
|
Both traveling cables are rubbing conduit in the hoistway. Move cables to prevent damage
|
10/29/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
Car light disconnect is located 9 feet up. Lower disconnect to where it is accessible
|
11/9/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
8.11.2.1.2(f)
|
|
|
Condensation line cannot be mounted over the pump unit in the elevator machine room. Move line
|
11/9/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.19 - Guide rails fastening and equipment
|
8.11.2.1.3(y)
|
|
|
Slide guides on the car top have excessive play and lateral movement. Adjust, replace, or repair slide guides
|
11/9/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19
|
|
|
Repair leaking victaulic pipe fitting inside the pump unit in the maching room.
|
11/9/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
Safety retainers are missing on top and bottom hoistway doors, need to install safety retainers. Re-inspection required
|
10/4/2024
|