Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room shall not be used for storage of non-elevator equipment. 9/30/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) AC unit cannot be located directly over the pump unit in the elevator machine room. Move AC unit 9/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Condensation line cannot be mounted over the pump unit in the elevator machine room. Move line 11/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.19 - Guide rails fastening and equipment 8.11.2.1.3(y) Slide guides on the car top have excessive play and lateral movement. Adjust, replace, or repair slide guides 11/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.35 - Supply Line and Shutoff Valve 3.19 Repair leaking victaulic pipe fitting inside the pump unit in the maching room. 11/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.5 - Traveling cables 8.11.2.1.5(f) Both traveling cables are rubbing conduit in the hoistway. Move cables to prevent damage 10/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Car light disconnect is located 9 feet up. Lower disconnect to where it is accessible 11/9/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.5 - Traveling cables 2.8.1 Both traveling cables are rubbing conduit in elevator hoistway. Move cables to prevent further damage 10/29/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Air conditioning systems shall not be located directly over elevator equipment. 9/8/2021
conversion conversion n/a Need "Low Overhead" clearly posted in hoistway 12/14/2018
conversion conversion n/a Post MO State operating permit in machine room 12/14/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 Cab ventilation not working. 9/30/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light not working. 6/15/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 x Safety retainers are missing on top and bottom hoistway doors, need to install safety retainers. Re-inspection required 10/4/2024