MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)1
|
|
|
Cab ventilation not working.
|
12/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light not working.
|
12/18/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell not working.
|
12/18/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Phone in the elevator cab does not work. Repair or replace
|
2/1/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room can not be used for storage of non elevator equipment
|
12/7/2021
|
A17.1-2016 : Elevators
|
1.14 - Ventilation
|
2.14.2.3
|
x
|
|
Elevator cab ventilation fan does not work on auxiliary power (battery power) needs repaired. Re-inspection required
|
10/4/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
3.19
|
|
|
Replace leaking victaulic fitting on hydraulic line in the machine room. Fitting is on the bottom side of the shut off valve
|
12/7/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated certificate in machine room.
|
12/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Need a maintenance control program on site
|
1/13/2022
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13 Door Systems
|
x
|
|
Safety retainers are missing on top & bottom hoistway doors, need to install safety retainers. Re-inspection required
|
10/4/2024
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.6.4.13.1(l)(Door Restrictor)
|
x
|
|
Elevator cab door restrictor does not work, needs repaired. Re-inspection required
|
10/4/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Oil line fitting going into tank leaking oil onto floor needs repair
|
1/13/2022
|