Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing is incomplete. Full load buffer testing, setting the safeties, and no load counterweight buffer test still need to be completed. 8/23/2023
MO Minimum : Elevators (A) - Hoistways (A)16 High voltage (110V) wiring on car top shall be enclosed in conduit. 1/4/2019
MO Minimum : Elevators (A) - Hoistways (A)16 Hoistway duct covers shall be installed. 1/4/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Car door restrictor does not work and shall be repaired. 1/4/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency light shall be operational. 9/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The alarm bell shall operate on auxiliary power. 9/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency telephone shall be operational. 9/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x The door restrictor shall be operational. 9/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Car top light does not work and shall be repaired. 1/4/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-locking and self-closing. 10/27/2020
MO Minimum : Elevators (H) - Machine Rooms (H)8 Traveling cables in the machine room shall be enclosed in wireway. 10/27/2020
MO Minimum : Elevators (I) - Pits (I)3 A counterweight guard shall be installed. 10/27/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work and shall be repaired. 1/4/2019
MO Minimum : Elevators (I) - Pits (I)8 Pit sump pump cover shall be installed flush with the pit floor. 1/4/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) Suspension rope data tags shall be installed. 1/4/2019
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Weight related testing of safeties, buffers, and machine brakes shall be completed. 11/8/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire service phase 1 & phase 2 key switches shall be legible. 9/22/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x The 3rd landing car call shall be operational on fire service phase 2. 9/22/2020
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage x x Fire service phase 1 instructions shall be posted at the hall key switch, and fire service phase 2 instructions shall be posted in the car. 9/22/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current state operating certificate shall be posted in the machine room in a non-combustible frame. 10/27/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 12/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current ABC type fire extinguisher shall be provided in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The machine room fire extinguisher shall be tagged to verify that the extinguisher is current. 10/27/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates A code data plate is required. 10/27/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Provide code compliant counterweight runby. 8/22/2023