Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Left-hand side handrail is cracked. 4/2/2019
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(H) The demarcation lights shall be operational. 7/26/2019
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate Display a current MO State operating certificate. 4/12/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/12/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.1 Escalator Handrails The left side handrail shall not have cracks. 3/10/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(E) Replace the broken comb segments at the bottom of the unit. 3/10/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Correct the source of the leaks at the drive machine gear box. 3/10/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x Unit failed skirt/performance index test. Make necessary corrections and re-test. 4/18/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.1 Escalator Handrails x Right handrail is cracked and showing extreme wear. The handrail shall be replaced. 7/25/2024