A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
|
|
The inside of the cab shall be labeled as "Elevator #1".
|
2/24/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light shall work, may need battery replacement.
|
8/24/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide phone to work
|
7/20/2022
|
A17.1-1996 : Elevators
|
1.8 - Door closing force
|
1001.2(a)(8)
|
x
|
x
|
Door closing force exceeded maximum allowed. RED TAGGED
|
8/24/2021
|
A17.1-1996 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
1001.2(b)(10)
|
|
|
The first floor elevator entrance shall be labeled as "Elevator #1".
|
2/24/2020
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
111
|
|
|
Door restrictor out of adjustment.
|
3/8/2024
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
One cab light bulb is not working.
|
2/24/2020
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
The cab light bulbs shall be guarded to contain glass if light breaks.
|
2/24/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone did not provide 2 way communication. May need to be reprogrammed.
|
8/24/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone line not working
|
6/20/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
post current certificate in machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current certificate.
|
3/8/2024
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(b)
|
|
|
Provide current year documents for the MCP.
|
3/8/2024
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Unsealed
|
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV is not sealed and must have a cat 5 weight test performed within 90 days or less
|
8/24/2021
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV unsealed, provide testing.
|
7/24/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV is not sealed or tagged. Perform required test on OSV within 90 days. Re-inspection required
|
|