Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/16/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Clean the pit. 8/26/2020
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) Determine the source of the corrosion where the hydraulic supply piping attaches to the cylinder. May be dissimilar metals. Re-Inspection required. 8/26/2020
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 Electrical box cover plate in pit is missing.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Pits shall be kept free of dirt and rubbish and shall not be used for storage purposes.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post the current state operating certificate. 8/26/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Provide a cover on the sump pump. 8/26/2020
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) Provide elevator numbering on the inside of the car. 8/26/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide means for emergency monitoring company to identify correct car number. 8/26/2020
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 1001.2(c)(15) Provide numbering of the car top. 8/26/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 3/15/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This unit is equipped with an overspeed valve and is due for category 5 testing in 2024.