Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Drop ceiling panels are open egg crate type, which provides no protection for passengers in event of bulb breakage. Replace with solid panels or install plastic tubes and end caps over bulbs 8/1/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Drop ceiling panels are open egg crate type, which provides no protection for passengers in event of bulb breakage. Replace with solid panels or install plastic tubes and end caps over bulbs. (noted on previous report)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x Battery lowering device inoperable, repair or replace as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light is not working. Re-inspection required 8/1/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 9/24/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. 9/24/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A copy of the MCP shall be kept in the machine room for each elevator 8/1/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current copy of the state operating certificate shall be displayed in elevator machine room 8/1/2022