Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Need maintenance control progrm including testing procedures in machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 Seismic (Earthquake protection) 8.4.10 x The ring on the counter-weight frame has been painted over so earthquake/seismic will not work. Take corrective action and re-test.
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 9/23/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Need a maintenance control program on site posted on controller 9/23/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection is incomplete: The car would not pick a full load. Governor needs to be adjusted as it is tripping to fast. Hoistway scan, SOS, fire service all still need to be tested. 11/29/2023
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Machine room needs more fire caulk on wall & top of door. 11/29/2023