Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 9/23/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No Need a maintenance control program on site posted on controller 9/23/2020
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 Yes No Machine room needs more fire caulk on wall & top of door. 11/29/2023
A17.1-2016 : Elevators 3.27 - Crosshead Data Plate and Rope Data Tags 8.10.2.2.3(k) No No Crosshead data tag shall be updated to reflect modernization that occurred in 2023. Car speed, capacity, rope data. (current car speed does not match the old crosshead data tag)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/7/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.42 Seismic (Earthquake protection) 8.4.10 Yes No The ring on the counter-weight frame has been painted over so earthquake/seismic will not work. Take corrective action and re-test. 1/29/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No Need maintenance control progrm including testing procedures in machine room 7/7/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Inspection is incomplete: The car would not pick a full load. Governor needs to be adjusted as it is tripping to fast. Hoistway scan, SOS, fire service all still need to be tested. 11/29/2023