MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
the 6 inch ledge at the back of the hoistway at the top landing floor should be beveled
|
2/18/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
In case of fire don't use elevator signage needed
|
7/8/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door must be self-locking
|
7/8/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
x
|
|
I (1) Water in the Elevator Pit sump pump quite working Replace the sump pump.
|
2/14/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Existing Pit Ladder needs replaced. Pit depth is 47.5 inches deep with the existing ladder hand holds of 24 inches above access landing sill, Which presents a safety hazard to enter pit for maintenance service.
|
5/31/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit of standing hydraulic oil.
|
2/18/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Provide a lamp for the pit light.
|
2/18/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Replace the cover for the sump hole.
|
2/18/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
replace missing light bulb in pit light
|
2/18/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
water in pit, sump hole is full, sump is not running
|
2/18/2023
|
conversion
|
conversion
|
n/a
|
|
|
ledge on wall of hoistway oposite of the car opening has a ledge that is greater than 4 inches and needs to be beveled
|
3/2/2023
|
conversion
|
conversion
|
n/a
|
|
|
clean oil spilled on the machine room floor
|
3/2/2023
|
conversion
|
conversion
|
n/a
|
|
|
adjust door close force to below 30 lbs, measured 32
|
3/2/2023
|