Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a adjust door close force to below 30 lbs, measured 32 3/2/2023
conversion conversion n/a clean oil spilled on the machine room floor 3/2/2023
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit of standing hydraulic oil. 2/18/2023
MO Minimum : Elevators (I) - Pits (I)5 Existing Pit Ladder needs replaced. Pit depth is 47.5 inches deep with the existing ladder hand holds of 24 inches above access landing sill, Which presents a safety hazard to enter pit for maintenance service. 5/31/2023
MO Minimum : Elevators (I) - Pits (I)1 x I (1) Water in the Elevator Pit sump pump quite working Replace the sump pump. 2/14/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates In case of fire don't use elevator signage needed 7/8/2024
conversion conversion n/a ledge on wall of hoistway oposite of the car opening has a ledge that is greater than 4 inches and needs to be beveled 3/2/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self-locking 7/8/2024
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Provide a lamp for the pit light. 2/18/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) replace missing light bulb in pit light 2/18/2023
MO Minimum : Elevators (I) - Pits (I)8 Replace the cover for the sump hole. 2/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements the 6 inch ledge at the back of the hoistway at the top landing floor should be beveled 2/18/2023
MO Minimum : Elevators (I) - Pits (I)1 water in pit, sump hole is full, sump is not running 2/18/2023