Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.14 - Code data plate 1200.6 An individual data plate shall be provided and maintained for each unit. The data plate shall indicate the code to be used for inspections and tests. The data plate shall indicate the code and edition in effect at the time of installation. The data plate shall also indicate the code in effect at the time of any alteration and indicate the applicable requirements of Section 8.7. The data plate shall be in plain view, securely attached to the main line disconnect or controller. 7/18/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room shall have self-closing and self-locking door and shall be operable from the interior space without the use of a key. It shall be kept locked. 7/10/2024
MO Minimum : Elevators (H) - Machine Rooms (H)1 A permanent and unobstructed means of access to the elevator machine room shall be provided. The pull-down ladder and the construction of the scuttle hole above the ladder leading to the roof do not look safe to use. Several of the ladder rungs appear to be falling apart. 7/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fire service phase one key-switch bezel shall be legible. 7/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Firefighters phase one instructions shall be posted near the phase one key-switch in the hallway at the egress floor. 7/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates A data plate shall be provided in the pit indicating the maximum designed counterweight run-by. 7/18/2024
MO Minimum : Elevators (N) - Guide Rails (N)1 A large (6 to 8 feet) section of the counterweight rail near the top landing has been partially removed. This may have a negative effect on the structural integrity of the installation and should be investigated. 7/10/2024
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting The machine room lighting shall be guarded. 7/10/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 The car-top lighting shall be guarded. 7/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The egress star on the car station is presently located next to the first landing car call and shall be located next to the third landing car call, since the phase one designated level is the third landing. 7/18/2024
MO Minimum : Elevators (A) - Hoistways (A)16 The junction box in the hoistway being used for the smaller of the two traveling cables shall be secured. 7/18/2024
MO Minimum : Elevators (A) - Hoistways (A)16 The cover missing from the raceway in the pit shall be replaced. 7/18/2024
MO Minimum : Elevators (A) - Hoistways (A)16 All the various broken/unsecured raceway fittings and broken flexible raceway on the car-top shall be replaced and corrected. 7/18/2024
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 A disconnect shall be provided for elevator lighting branch circuit. It shall be capable of being locked in the open position and shall be located in the machine room. 7/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts The car operating panel is currently secured with only one fastener. The other fasteners shall be replaced. 7/18/2024
A17.1-1996 : Elevators 3.17 - Door and gate equipment 110 The upthrusts are missing on some of the hall door hangers and shall be replaced (the auxiliary retaining devices are in place). 7/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Fasteners are missing from some of the interlock covers and shall be replaced. 7/18/2024
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The stairs that lead to the roof of the building, where the elevator machine room is located, are unsafe and require corrective action. Provide code compliant access to the roof and machine room. 6/9/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/1/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) The governor rope and the hoist ropes shall have data tags installed. 7/1/2021
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 1001.2(c)(18) The hoistway junction box at the 3rd floor shall be properly secured. 7/1/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) Provide safe access to the roof/machine room. 7/1/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The machine room door shall be self-closing and self-locking. 7/1/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean. 12/12/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit shall be kept clean. Clean the pit. 5/4/2023
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) Top of car needs to be cleaned off. 5/4/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) x The emergency/standby power shall be tested. The building was not prepared to test this. It will have to be rescheduled. 7/2/2024
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x The suspension ropes need to be shortened. 4/26/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x The smoke detector shall be properly attached to the ceiling in the machine room. 8/30/2022
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x The hoist cables are rouged and nearing the minimum acceptable diameter and shall be replaced within 90 days. 8/30/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 8/30/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x The smoke detector shall be properly attached to the ceiling in the machine room. 9/28/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 9/28/2022