Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No post current state certificate in the machine room 12/8/2025
A17.1-1996 : Elevators 3.23 - Suspension rope 212 Yes No Replace Ropes - Red Rouge & reduced diameter- Within 30 Days 12/8/2025
A17.1-1996 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 1206.7 Yes Yes Perform Monthly Fire service test and document on the log posted in the Machineroom 12/8/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/22/2024
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. 11/22/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 8/16/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service and document on log in machine room 8/16/2023
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b No No Repair machine room air conditioner 8/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace missing isolation pad on rope shackle in machine room 8/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Provide a maintenance control plan. 8/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Repair seismic operation 8.4.10.1.1 8/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Need testing procedures located in the MCP on or by January 1, 2022 8/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Isolation pads needs replacing 8/16/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors No No Floor tiles broken and loose needs to be repaired 8/16/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned 8/16/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors No No Replace broken car floor tile 8/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Repair phone in car 5/12/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No When simulating 1st floor smoke detector car failed to respond 5/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Repair car floor tile--tripping hazard 11/11/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide maintenance control program and place on controller in machine room 11/11/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service test and document on log in machine room 11/11/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Repair seismic operation within 30 days--reinspection required 11/11/2020
conversion conversion n/a No No Replace cracked floor tile in car, tripping hazard 9/25/2018
conversion conversion n/a No No Post current State cetificate in machine room 9/25/2018
conversion conversion conversion - reinspect Yes No Repair Fire Service--when simulating smoke dector--car did not respond 9/24/2018