Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 3.23 - Suspension rope | 206.7 | x | Shorten hoist ropes. Counterweight buffer is being compressed 4" when car is at top landing. | 8/2/2019 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab is not working, needs repaired. Re-inspection required | 7/18/2024 |