Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Testing procedures are missing from the MCP.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(b) On-Site Maintenance Records (Repair and Replacement Records) Repair records are missing from the MCP.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall work. 10/30/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering does not work. (2nd Notice) This violation must be correct ASAP or the unit may be locked out of service until corrected.
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. (2nd Notice) This violation must be correct ASAP or the unit may be locked out of service until corrected.
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 10/30/2024
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals x The hydraulic cylinder packing is leaking excessively and corrective action shall be taken. 6/27/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.